Setup a „Constant Signal“ for the angle where to test the force:
- set the value for the constant signal (here: 300)
- choose an Internal ID (here: 72)
Trigger output
In this example, the overpassing of an angle initiates an output signal if the force is in between specific limits.
Setup a „Constant Signal“ for the angle where to test the force:
Setup a „Constant Signal“ for the force threshold:
Setup a „Trigger Pulse“ which initiates a pulse at the output Flag01 when the angle crosses the 300°:
Setup a „Trigger Range“ which sets the output Flag02 when the force is between 0 and 200N:
Setup a “Logic function” which sets Flag 03 if Flags 01 and 02 are set too (Flag03 = Flag01 AND Flag02):
Setup a “Timer” to create a low-pulse in Flag 04 for 0.3s:
Digital Output: Connect Flag 04 with output 4 (can be any other output) Please note the output is inverted to get a high-pulse.
PX460 settings: Angle is measured by an encoder with 1024 pulses per revolution. (Encoder with one single track connected to pin 3 and GND)
These examples are simply for the purpose of illustration. They cannot be used as the basis for any warranty or liability claims.